How does a monoflange work?

Monoflanges combine the event of up to three valves in a particularly compact body, because of a precise network of internal passages and valve chambers. But what really happens inside a monoflange valve, once installed?
In Special is required for some control applications. One of many variables that affect the response time may be the volume and the length between process and instruments. If the medium to be measured is gas, and the procedure tends to fluctuate strongly sometimes or if the control is critical, mounting the instrument near the process may be the solution.
Vibrations are also critical, for example, in case that impulse lines are connected to a vessel. The longer the hook-up, the wider is the amplitude of the vibration causing possible failures of the nozzle. A monoflange includes one, several needle valves in the compact, flange-shaped body, allowing a substantial decrease in volume, dimensions, weight and potential leakage points.
Monoflange may be the solution
With regards to the requirements of the plant it is installed in, the monoflange can incorporate one, several valves. In a monoflange with two valves (block & bleed), one valve (with a blue cap) isolates the process and the other (with a red cap) regulates the venting of the medium trapped inside the instrument. That is mostly used in applications which are relatively uncritical (e.g. low pressure) or where a first shut-off valve is provided right before the monoflange.
The safest configuration, and the main one we advise for aggressive media or critical operating conditions, is the three-valve monoflange or the so-called double block & bleed (DBB), which features two shut-off valves in series and something valve for venting.
Monoflange functionality
The monoflange bodies are drilled internally with holes which connect the annular valve chambers.
The next picture illustrates the procedure within a DBB monoflange:
The flow enters the monoflange from the pipeline and stops below the first shut-off valve [1];
When the first shut-off valve [1] opens, the flow proceeds towards the second shut-off valve [2] ; when the valve [2] is open, the instrument is thus linked to the process line;
Once the first shut-off valve [1] is closed, the medium trapped between valve and instrument could be discharged via the vent valve [3] through the vent outlet. The two shut-off valves [1, 2] are in an angled position, that allows the flow to feed them.
The two shut-off valves allow an improved isolation from the procedure: In case the first shut-off valve will not isolate the medium properly, the second one will become a safety means against accidental leaks. Sometimes, customer specifications do not allow the medium to be in touch with the instrument when it is not measuring. That is why the medium will be discharged using the vent line. In other cases ? as a result of vent line ? instruments could be easily calibrated without dismounting them from the line.